Repair and Maintenance

  General

A good maintenance program is the key to extending the genset's lifetime. Maintenance and service should only be operated by qualified technicians. Records of this work should be kept to develop an efficient maintenance program.

 Generator Set Preventative Maintenance

Cheak before starting every time
(For standby sets these procedures may be performed weekly.) A walk around inspection should be performed on a daily basis and prior to starting the engine. 


Every two weeks
(For standby sets that have not been run.) Perform an operational check on the generating set by starting and running the set for only takes 5 minutes. WARNING: don't run diesel engines at low loads for long periods.

Every month
(For standby sets that have not been run on load.) Perform an operational check on the generating set by starting and running the set on at least 50% load takes 1 to 2 hours.
Every six months or 250 hours

Repeat the daily procedures, as follows:
Check all control system safety devices by electrically simulating faults.
Clean all battery cap vents.
Tighten all exhaust connections.
Tighten all electrical connections.
Perform other engine maintenance as specified in the engine manual.
Start the engine and observe the instrument panel to ensure that all gauges and meters are operating properly.